Listing 3130001:No. 15 Steam Turbine Generator Set (SD 15G)

DATA SHEET AVAILABLE FOR DOWNLOAD HERE


For sale by private treaty: the No. 15 steam turbine generator set at Daio Paper Corporation's Mishima Mill, Japan – Shin Nippon Machinery turbine C11-R16-EX, 62,920 kW, and MEIDEN generator TIC-AFT, 69,912 kVA, built 2019.

Buyers Premium: 18%

Tax Rate on Hammer Price: 10%

Listed Until Dec 18, 2026, 5:00 PM UTC
Register for Auction

Description

1. Scope and site

Item

Data

Owner / site

Daio Paper Corporation (大王製紙株式会社), Mishima Mill

Unit

No. 15 steam turbine generator set (15号機)

Scope of sale

Steam turbine and generator; associated accessories can be included on request

Not included

Boiler

Steam parameters (owner's data)

8.6 MPa / 512 °C / 236 t/h

Rated output

Turbine 62,920 kW; Generator 69,912 kVA

Delivery year of the generating equipment

2020 (per MEIDEN maintenance plan for the generator control panel)

2. Steam turbine

Item

Data

Manufacturer

Shin Nippon Machinery Co., Ltd. (新日本造機株式会社)

Type

C11-R16-EX, multi-stage (16 stages)

Main unit serial no.

DIOSM-3A-11893

Rated output

62,920 kW

Steam parameters (owner's data)

8.6 MPa / 512 °C / 236 t/h

Exhaust

To condenser

Main steam stop valve

Emergency trip valve (MSV)

Governing valve

HP steam control valve, venturi type, 5 valves, servo-motor actuated

Turbine–generator coupling

Diaphragm coupling; face-to-face distance 550 mm (design +0.2/+0.5 mm; measured 550.32 mm, June 2024)

Turning device

Fitted

Lube oil system

Main oil pumps No. 1 and No. 2, type HG-65MT (motor driven); emergency oil pump type NHG-10 (motor driven); control oil pumps No. 1 and No. 2 (No. 2 motor driven)

Protection

Manual trip cock; remote trip device incl. solenoid valve

Bearing clearances (May 2024)

Journal 0.48 / 0.47 mm (management value 0.34–0.48); thrust 0.71 mm (management value 0.58–0.74)

3. Generator

Item

Data

Make

MEIDEN – OEM reports by Meiden Engineering Corporation; generator control panel manufactured by Meidensha (明電舎)

Type

TIC-AFT

Rated capacity

69,912 kVA

Voltage / frequency

11,000 V / 60 Hz

Poles / speed

2-pole / 3,600 min⁻¹

Serial no.

4B6490R1

Year of manufacture

2019

Excitation

AC exciter with rotating rectifier and PMG (permanent magnet generator)

Cooling

Air cooler with water-cooled tubes; flange gaskets 10K-150A-t2 (replaced 2024)

Bearings

Bearing metal with labyrinth seals, oil lubricated; bearing box at negative pressure in operation

Shaft voltage (18 Sept 2025)

900 mV AC, NDE bearing to ground, at 11,000 V no-load – judged good

Generator control panel

Meidensha, S/N 2A7149PB, built 2019, installed in the electrical room; AVR, digital protection relays, transducers, sequencer

Insulation resistance (13 Sept 2025)

Stator 200 MΩ (1,000 V megger; criterion ≥ 10 MΩ); main field, rotating rectifier, exciter armature, exciter field and PMG ≥ 1,000 MΩ (500 V megger)

4. Inspection and maintenance history (newest first)

Period

Work

Contractor / document

Result

11–13 Sept 2025, test run 18 Sept 2025

Unscheduled generator internal cleaning (report title “突発 SD”): oil accumulation removed inside generator, exciter and PMG; oil leak outside the air cooler cleaned; insulation resistance, vibration, temperature rise, bearing box pressure, shaft voltage; load test to 56.44 MW

Meiden Engineering, report 0-220R25244

No abnormality found that would lead to an oil leak; load test judged good; periodic cleaning recommended

16–17 May 2024, start-up 12 June 2024

First periodic inspection of generator control panel / AVR: switchboard inspection, protection relay tests, insulation resistance, interlock tests, AVR static, no-load and load checks

Meiden Engineering, report 0-250R24109

No abnormalities

15–23 May 2024

Generator disassembly and detailed inspection with rotor withdrawn; insulation diagnosis; air cooler inspection (eddy current test, 30-min hydrostatic test, gaskets replaced); test run incl. ozone measurement

Meiden Engineering, report 0-220R24216 + photo album

No abnormalities; insulation judged sufficient for operation

8 May – 12 June 2024 (36 days)

Turbine periodic overhaul: casing opened; rotor, nozzles, bearings, valves inspected; clearance and alignment records; oil pumps serviced; safety and operation tests

Shin Nippon Machinery, job DIOSM-6M-82040, report dated 17 June 2024

All inspected items judged ○ (pass); repairs and OEM recommendations in section 5

5. Turbine overhaul 2024 – findings, repairs, OEM recommendations

•     Slight erosion (length 10 mm) at the tips of the last-stage (16th) blades – to be monitored over time.

•     Erosion at upper- and lower-half nozzles, stages 12, 13 and 14 – weld-repaired and hand-finished by the customer; to be monitored over time.

•     Labyrinth and rotor fin damage at clearance-table positions C, D, E, F – hand-finished; rotor fin wear exceeds the management value, so the OEM recommends replacing the rotor fins together with the labyrinths.

•     Governing valve: crack in the weld of the 1st valve seat, weld-repaired by the customer (PT good); gland packing replaced.

•     Main steam stop valve: sub-valve cover could not be loosened and was not disassembled – OEM recommends servicing at the Kure works (呉工場) next time; damage to the valve cover and sub-valve bush hand-finished, replacement recommended next time; hydraulic relay and oil cylinder not disassembled this time, disassembly recommended next time.

•     Servo motor not serviced this time; OEM recommends manufacturer servicing next time.

•     16 main steam flange bolts and 3 coupling spacer reamer bolts replaced; turbine–generator alignment adjusted.

•     Main oil pumps No. 1/No. 2 and emergency oil pump serviced under the pump manufacturer's guidance (measurements, coupling, pump–motor alignment, motor and operation checked); control oil pump No. 2 replaced by a new unit, one unit serviced and kept as spare.

•     Turning device initial torque changed from 10 % to 20 %.

•     Recommended spare parts list for the next overhaul (MSV parts, governing valve packings, carbon brushes) included in the report.

6. Generator test data

Load test, 18 Sept 2025: 56.44 MW, 11,020 V, 2,999 A, power factor 98.40 %, exciter field 34.0 V / 7.2 A; stator winding U/V/W 62.6 / 63.8 / 63.0 °C; bearings DE 61.1 °C, NDE 63.4 °C; lube oil 46.6 °C at 102.1 kPa; cooling water in/out 29.8 / 32.0 °C. Criteria: stator temperature rise ≤ 100 K, bearing temperature ≤ 80 °C – judged good.

Vibration at 56,800 kW: bearings max. 8.3 µm p-p, casings max. 11.2 µm p-p (criterion for bearing pedestals ≤ 40 µm); shaft max. 36/50 µm p-p X/Y at DE (criterion ≤ 100 µm).

Insulation diagnosis, May 2024: stator insulation resistance U/V/W 28,860 / 31,250 / 31,250 MΩ (1-min values, DC 1 kV applied for 10 min), polarisation index 7.00 / 5.93 / 6.28; rotor 100 MΩ (DC 0.5 kV); tan δ0 at 2 kV 1.36 / 1.15 / 1.10 %; partial discharge Qmax 2,400 / 3,000 / 2,500 pC – all within the criteria.

7. Documentation available (in Japanese)

•     Shin Nippon Machinery working report, turbine periodic inspection and maintenance, dated 17 June 2024 (checklists, clearance tables, bearing and alignment records, photos, spare parts list)

•     Meiden Engineering report 0-220R24216, generator disassembly/assembly and detailed inspection, June 2024, plus photo album

•     Meiden Engineering report 0-250R24109, generator control panel / AVR inspection, maintenance and repair, June 2024

•     Meiden Engineering report 0-220R25244, unscheduled generator internal cleaning (“突発 SD”), September 2025

 